The present study presents the experimental study of performance of the displacement ventilation . The experimental study included the effect of different internal loads of (1600,1300and 1000)W , different supplied air temperatures of ( 18,20,22and 24)?C and different supplied air velocities (0.75,1,1.25 and 1.45)m/s on the performance of displacement ventilation . The experimental results show that the cooling capacity of air increases as the temperature of supplied air decreases. At a increases in temperature of supplied air by (33.33)%,the cooling capacity of air decreases by (23.52, 24.05 and 20.63)% for internal load of (1600,1300 and 1000 )W respectively .While as supplied air velocity increases ,the cooling capacity of air increases .At supplied air increases by (93.33)% ,the cooling capacity increase by (33.61, 39.23 and 36.8 )% for internal load of (1600, 1300 and 1000)W respectively.
Keywords
Article Analytics
References
- Rehva (2002)" Displacement Ventilation Guidebook"
- Nielsen(1996)" Temperature Distribution in a Displacement Ventilated Room" Indoor Environmental Technology; No. 67, Vol. R9659
- Yin ,W.Xu,J.K..Gupta,A.Guity,P.Marmion ,A.Manning ,B.Gulick,X .Zhanga a nd Q.Chen (2009)" Experimental Study on Displacement and Mixing Ventilation Systems for a Patient Ward" HVAC&R Research,15(6), 1175-1191
- Nuno M. ?. Mateus and Guilherme Carrilho Da Graca (2017)" Simulated and measured performance of displacement ventilation systems in large rooms" Building and Environment?114???January 2017
- S. P. Silva, M. A. Sabino, E. M. Fernandes, V. M. Correlo, L. F. Boesel? and R. L. Reis (2005)" Cork: properties, capabilities and applications " International Materials Reviews? 2005 VOL 50 NO 6 347
- Cunha et al ,2008," Fan and Blowers Energy Efficiency and Reference Guide"
- Hidria,2011, " Circular diffuser and Square diffuser Guide"
- INNOVA Air TECH Instruments (2002)"Thermal comfortable "
- Bauamn (2012)" Thermal Comfort Research at the Center for the Built Environment Center for the Built Environment (CBE)" the University of California
- Nadine Walikewitz a, Britta Janicke, Marcel Langner, Fred Meier and Wilfried Endlicher ((2015)," The difference between the mean radiant temperature and the air temperature within indoor environments: A case study during summer conditions" Building and Environment 84 (2015) 151-161.
How to Cite This Article
Israa Ali AbdulGhafor, Adnan. A. Abdulrasool and Qasem S. Mehdi. (2018); EXPERIMENTAL STUDY TO THE PERFORMANCE OF THE DISPLACEMENT VENTILATION UNDER DIFFERENT OPERATION CONDITIONS., Int. J. of Adv. Res., 6 (06), 485-494, ISSN 2320-5407. DOI: https://doi.org/10.21474/IJAR01/7235
Corresponding Author
This work is licensed under a Creative Commons Attribution 4.0 International License.