Vol. 6 (06) pp. 485-494 DOI: 10.21474/IJAR01/7235

EXPERIMENTAL STUDY TO THE PERFORMANCE OF THE DISPLACEMENT VENTILATION UNDER DIFFERENT OPERATION CONDITIONS.

  • Ph student.
  • Prof. Mechanical Engineering Department, Al Mustansiriayah University, Baghdad, Iraq.
15 Downloads 80 Views
Crossref

Abstract

The present study presents the experimental study of performance of the displacement ventilation . The experimental study included the effect of different internal loads of (1600,1300and 1000)W , different supplied air temperatures of ( 18,20,22and 24)?C and different supplied air velocities (0.75,1,1.25 and 1.45)m/s on the performance of displacement ventilation . The experimental results show that the cooling capacity of air increases as the temperature of supplied air decreases. At a increases in temperature of supplied air by (33.33)%,the cooling capacity of air decreases by (23.52, 24.05 and 20.63)% for internal load of (1600,1300 and 1000 )W respectively .While as supplied air velocity increases ,the cooling capacity of air increases .At supplied air increases by (93.33)% ,the cooling capacity increase by (33.61, 39.23 and 36.8 )% for internal load of (1600, 1300 and 1000)W respectively.

Keywords

Article Analytics

References

  1. Rehva (2002)" Displacement Ventilation Guidebook"
  2. Nielsen(1996)" Temperature Distribution in a Displacement Ventilated Room" Indoor Environmental Technology; No. 67, Vol. R9659
  3. Yin ,W.Xu,J.K..Gupta,A.Guity,P.Marmion ,A.Manning ,B.Gulick,X .Zhanga a nd Q.Chen (2009)" Experimental Study on Displacement and Mixing Ventilation Systems for a Patient Ward" HVAC&R Research,15(6), 1175-1191
  4. Nuno M. ?. Mateus and Guilherme Carrilho Da Graca (2017)" Simulated and measured performance of displacement ventilation systems in large rooms" Building and Environment?114???January 2017
  5. S. P. Silva, M. A. Sabino, E. M. Fernandes, V. M. Correlo, L. F. Boesel? and R. L. Reis (2005)" Cork: properties, capabilities and applications " International Materials Reviews? 2005 VOL 50 NO 6 347
  1. Cunha et al ,2008," Fan and Blowers Energy Efficiency and Reference Guide"
  2. Hidria,2011, " Circular diffuser and Square diffuser Guide"
  3. INNOVA Air TECH Instruments (2002)"Thermal comfortable "
  4. Bauamn (2012)" Thermal Comfort Research at the Center for the Built Environment Center for the Built Environment (CBE)" the University of California
  5. Nadine Walikewitz a, Britta Janicke, Marcel Langner, Fred Meier and Wilfried Endlicher ((2015)," The difference between the mean radiant temperature and the air temperature within indoor environments: A case study during summer conditions" Building and Environment 84 (2015) 151-161.

How to Cite This Article

Israa Ali AbdulGhafor, Adnan. A. Abdulrasool and Qasem S. Mehdi. (2018); EXPERIMENTAL STUDY TO THE PERFORMANCE OF THE DISPLACEMENT VENTILATION UNDER DIFFERENT OPERATION CONDITIONS., Int. J. of Adv. Res., 6 (06), 485-494, ISSN 2320-5407. DOI: https://doi.org/10.21474/IJAR01/7235

Corresponding Author

Israa Ali Abdulghafor
Mechanical engineering